Relays for Transmission & Distribution Lines protection:
| No | Line | Protection | 
| 1 | 400 KV Transmission Line | Main-I: Non switched or Numerical Distance Scheme | 
| Main-II: Non switched or Numerical Distance Scheme | ||
| 2 | 220 KV Transmission Line | Main-I : Non switched distance scheme (Fed from Bus PTs) | 
| Main-II: Switched distance scheme (Fed from line CVTs) With a changeover facility from bus PT to line CVT and vice-versa | ||
| 3 | 132 KV Transmission Line | Main Protection: Switched distance scheme (fed from bus PT). | 
| Backup Protection: 3 Nos. directional IDMT O/L Relays and 1 No. Directional IDMT E/L relay.  | 
||
| 4 | 33 KV Lines | Non-directional IDMT 3 Over Current and 1 Earth Fault relays | 
| 5 | 11KV Line | Non-directional IDMT 2 Over Current and 1 Earth Fault relays | 